1.0 Subject
Marshall Extend-O-Column
Marshall Fixed Length Column
2.0 Research Scope
2.1 Building Codes:
2009 International Building Code (IBC)
2009 International Residential Code (IRC)
2.2 Properties:
Structural
Corrosion protection
3.0 Description
3.1 General – The Marshall Extend-O-Column
and Marshall Fixed Length Columns are
adjustable and fixed columns constructed of
carbon steel for use in supporting loads in
wood frame and light steel frame
construction. The column sizes that are
recognized in this report are listed in Tables
A through H. Refer to Figure 1 for column
details.
3.2 The posts are fabricated from the steel
grades listed below.
• Tube - ASTM A500 Grade B, Carbon Steel
• Flange - ASTM A36 Hot-Rolled Carbon
Steel
• Screw - AISI 1117 Carbon Steel
3.3 Corrosion protection - All Marshall Stamping
steel column sections are protected with a
rust inhibiting enamel applied to all surfaces
including the inside of the column.
3.4 The columns, both fixed length and
adjustable, are produced in the following
diameters – 3.0, 3.5 and 4.0 inches with
either an 11 gauge or 0.216 inch thickness.
Refer to Tables A through H.
|
3.5 The adjustable columns are available in
lengths from six (6) feet to twelve (12) feet,
four (4) inches as designated in Tables A
through D.
3.6 The fixed length columns are available in
lengths from five (5) feet, nine (9) inches to
twelve (12) feet as designated in Tables E
through H.
4.0 Installation
4.1 Installation shall be in accordance with the
applicable code, manufacturer's installation
instructions and this report. Where
differences occur between this report and the
manufacturer's installation instructions, this
report shall govern.
4.2 The Marshall Stamping Extend-O-Column
must be installed with the adjustable screw
mechanism on the bottom. The entire
adjustment mechanism, including the entire
collar nut, shall be encased in minimum 3500
psi concrete.
5.0 Supporting Evidence
5.1 Manufacturer's drawings and installation
instructions.
5.2 Engineering calculations in accordance with
American Institute of Steel Construction
(AISC) 360-05, Specification for Structural
Steel Buildings.
5.3 Reports of load testing in accordance with
ASTM E 72.
5.4 Quality control manual in accordance with
ICC-ES Acceptance Criteria for Quality
Documentation, (AC10.)
6.0 Conditions of Use
6.1 The steel columns identified in this report are
deemed to comply with the referenced
building codes subject to the following
conditions.
6.2 Steel column structural elements shall be
designed to safely support applicable loads
and load combinations in accordance with
Chapter 16 of the IBC. |